Water Quality

Below are the latest results for the testing of Disinfection Byproducts for the Village of Whitehouse.

The Maximum Contaminant Level (MCL) has been established as 80 ug/L.

Disinfection Byproducts

*all values are ug/L

 

Sample Site 3rd Qtr 2018 4th Qtr 2018 1st Qtr 2019 2nd Qtr 2019 Annual Average
Entry Point Texas St 56.0 33.8 55.1 86.2 57.8
Entry Point Dutch Rd 63.9 27.6 36.2 88.9 54.2
Sample Site 1 87.2 63.8 76.4 64.5 73.0
Sample Site 2 83.3 65.7 58.6 26.9 58.6
Water Tower Gilead St 74.9 45.4 48.3 20.9 47.4
Water Tower Finzel Rd 66.4 43.3 46.7 20.4 44.2
Detailed Results 3rd Qtr 2018 Results 4th Qtr 2018 Results 1st Qtr 2019 Results 2nd Qtr 2019 Results

We are confident that with continued weekly flushing of hydrants in the distribution system to keep water fresh, that these numbers will remain below the MCL for the coming quarters.

The Village has contracted with Poggemeyer Design Group of Bowling Green, Ohio to draft engineering specifications for a water tower mixing/aeration system to facilitate the release of trihalomethanes (THMs) in the water towers and reduce the formation or growth of THMs in the distribution system.  The Village’s permanent solution for a THM removal system should be installed and operational by November 2018.

If you have any questions or need clarification, please contact Steve Pilcher at 419.877.5383.

Water Quality Report

Each year, the Village is required to publish a copy of the Water Quality Report for the previous year.  Click below for a copy of the most recent Water Quality Reports:

Here is a link to the most recent Toledo Water Quality information: 

April, 2016 – Ohio EPA introduces a new Harmful Algal Bloom (HAB) Advisory System